tankvolumecalc.com
Home / Tank sizes / 1000 Gallon Underground Oil Tank
1000 gal · dimensions

1000 Gallon Underground Oil Tank dimensions

A typical 1000 gallon underground oil tank is 48 in in diameter and 130 in (10.8 ft) long. Usually filled to ~900 gal.

Measurements differ from the standard ones below? The horizontal tank volume calculator works out gallons at any fill depth for your own tank.

Dimensions, capacity & weight
SpecValue
Diameter48 in
Length130 in (10.8 ft)
Geometric capacity1,018.4 gal
Nominal rating1000 gal
Liquid weight (brim-full)7,332 lb of heating oil #2
Empty tank weightVaries by gauge/manufacturer — see nameplate or spec sheet

Nominal rating versus real geometry

Rated 1,000 gal. Computed from the dimensions in the table above: 1,018.4 gal. The shell is built oversize by 18.4 gallons — 1.8 % — against its label. That headroom is deliberate: it is ullage for thermal expansion and outage, not capacity you are meant to use.

1000 Gallon Underground Oil Tank — weight of contents at the stated capacity
ContentsDensityWeight of contentsMetric
Water8.35 lb/gal8,499 lb3,855 kg
No. 2 heating oil7.20 lb/gal7,332 lb3,326 kg
Diesel7.05 lb/gal7,180 lb3,257 kg
Gasoline6.30 lb/gal6,416 lb2,910 kg

Densities are the reference values on our methodology page; add the empty vessel weight for a gross figure.

What is the same for every tank of this kind (siting, backfill and access, the standards behind underground oil tanks) is set out once on the sizes hub, in the underground oil tank reference and the common questions for every tank.

Stick readings at quarter levels

The table uses the 48 in × 130 in cylinder on this page. It gives the stick reading for each quarter of the brim-full volume (1,018 gal).

1000 gal underground tank (48 × 130 in): depth for each quarter
LevelStick readingUS gallons
1/4 tank14.3 in255
1/2 tank24.0 in509
3/4 tank33.7 in764

Half the volume is at half the diameter. One quarter of the volume is lower than one quarter of the diameter, because the bottom of the tank is narrow.

How to stick an underground tank

  1. Find the fill pipe. Remove the cap.
  2. Put a long, clean wooden stick down the fill pipe until it touches the bottom of the tank. Keep the stick vertical.
  3. Remove the stick and read the wet line, measured from the bottom end.
  4. Find the reading in the horizontal tank calculator with this tank's diameter and length.
  5. Install the cap again.

If the stick touches at an angle, the fill pipe is not vertical above the tank. The reading is then too deep. For more methods, see how to measure an underground tank.

Federal rules

40 CFR 280.12 defines an underground storage tank for the federal UST rules. The definition excludes a tank that stores heating oil for use on the premises where it is stored. State and local rules can still apply. Ask your state environmental agency.

Dimension drawing

END VIEWD = 48 inSIDE VIEWL = 130 inh
Diameter 48 in, length 130 in. Geometry used for the chart. The shaded area shows an example liquid level. The drawing is not to scale.

FAQ

What are the dimensions of a 1000 gallon underground oil tank?

As modelled on this page: diameter 48 in, length 130 in (10.8 ft). Check your tank's nameplate or data sheet; a particular maker's tank can differ.

How much does a full 1000 gallon underground oil tank weigh?

About 8,499 lb of water, or less for a hydrocarbon — the weight table above gives the figure for each liquid. Add the empty vessel weight for a gross figure.

Sources and standards

  1. 40 CFR § 280.43 — Methods of release detection for tanksU.S. Environmental Protection Agency, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-I/part-280/subpart-D/section-280.43
  2. 40 CFR Part 280 — Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage TanksU.S. Environmental Protection Agency, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-I/part-280
  3. UL 80 — Standard for Steel Tanks for Oil-Burner Fuel and Other Combustible Liquids; UL 58 — Steel Underground Tanks for Flammable and Combustible LiquidsUL Standards & EngagementPaid standard — cited by designation; obtain from the publisher.
  4. NFPA 31 — Standard for the Installation of Oil-Burning EquipmentNational Fire Protection AssociationPaid standard — cited by designation; obtain from the publisher.
  5. Handbook 44, Appendix C — General Tables of Units of MeasurementNational Institute of Standards and Technology, U.S. Department of Commercehttps://www.nist.gov/document/2026-nist-handbook-44-appendix-c
  6. ISO 7507-1 — Petroleum and liquid petroleum products: Calibration of vertical cylindrical tanks, Part 1: Manual strapping methodInternational Organization for StandardizationPaid standard — cited by designation; obtain from the publisher.
  7. Methodology — the partial-fill formulas and liquid densities used on this sitetankvolumecalc.comhttps://tankvolumecalc.com/methodology/

Every linked source above was retrieved and checked on 2026-09-02.