Tank sizes & dimensions.
Verified dimensions for every standard tank, with capacities from exact geometry, liquid weights, and the clearance rules that apply.
Standard tanks
275 Gallon Oil Tank (Vertical or Horizontal)
27″W × 44″H × 60″L
330 gal330 Gallon Oil Tank (Vertical or Horizontal)
27″W × 44″H × 72″L
500 gal500 Gallon Underground Oil Tank
48″ dia × 64″
550 gal550 Gallon Underground Oil Tank
42″ dia × 92″
1000 gal1000 Gallon Underground Oil Tank
48″ dia × 130″
120 gal water capacity120 Gallon Propane Tank
24″ dia × ~64″ overall
250 gal water capacity250 Gallon Propane Tank
30″ dia × ~85″ overall
500 gal water capacity500 Gallon Propane Tank
37.5″ dia × ~108″ overall
1000 gal water capacity1000 Gallon Propane Tank
41″ dia × ~179″ overall
55 gal55 Gallon Drum
22.5″ dia × 33.5″
275 gal275 Gallon IBC Tote
45″ × 40″ × 35.3″
330 gal330 Gallon IBC Tote
48″ × 40″ × 39.7″
1500 gal1500 Gallon Underground Oil Tank
64″ dia × 108″
2000 gal2000 Gallon Underground Oil Tank
64″ dia × 144″
320 gal water capacity320 Gallon Propane Tank
30″ dia × ~108″ overall
10 gal10 Gallon Aquarium
20″ × 10″ × 12″
20 gal20 Gallon High Aquarium
24″ × 12″ × 16″
29 gal29 Gallon Aquarium
30″ × 12″ × 18″
40 gal40 Gallon Breeder Aquarium
36″ × 18″ × 16″
55 gal55 Gallon Aquarium
48″ × 13″ × 21″
75 gal75 Gallon Aquarium
48″ × 18″ × 21″
125 gal125 Gallon Aquarium
72″ × 18″ × 21″
Propane cylinders
More aquariums, farm & septic
5 Gallon Aquarium
16¼″ × 8⅜″ × 10½″
20 gal20 Gallon Long Aquarium
30¼″ × 12½″ × 12¾″
60 gal60 Gallon Aquarium
Breeder 48½″ or 24″ cube
100 gal100 Gallon Aquarium
48″ × 18″ × 24″
120 gal120 Gallon Aquarium
48″ × 24″ × 24″
5 gal5 Gallon Bucket
11.8″ top × 14.4″ tall
STOCKStock tank sizes
Round, oval & poly — up to 10 ft
SEPTICSeptic tank sizes
Minimums by bedrooms, 8 states
By capacity (any tank)
100 gallon tank
Every diameter/length that holds it
150 GAL150 gallon tank
Every diameter/length that holds it
200 GAL200 gallon tank
Every diameter/length that holds it
250 GAL250 gallon tank
Every diameter/length that holds it
300 GAL300 gallon tank
Every diameter/length that holds it
400 GAL400 gallon tank
Every diameter/length that holds it
600 GAL600 gallon tank
Every diameter/length that holds it
750 GAL750 gallon tank
Every diameter/length that holds it
2500 GAL2,500 gallon tank
Every diameter/length that holds it
3000 GAL3,000 gallon tank
Every diameter/length that holds it
Three different numbers, all called "capacity"
Almost every argument about tank size is really an argument about which of these three figures someone is quoting.
- Nominal rating. The trade label — "275 gallon", "55 gallon". It is a name, chosen for being memorable and round. Nothing obliges it to match anything.
- Geometric capacity. What the stated dimensions actually hold, brim full, computed exactly. This is the figure in each size table here, and it is frequently a few percent away from the label in either direction.
- Usable capacity. What you can actually put in and get out. Subtract the ullage kept for thermal expansion, the dead volume below the outlet, and for propane the 80 % filling limit. On a propane vessel this is the number that matters and it is never the one on the nameplate.
The nameplate governs for anything built to a listing standard — an ASME propane vessel, a UL 80 oil tank, a UN-marked drum or IBC. For those, the stamped or moulded capacity is authoritative and a tape measure is a cross-check, not a correction.
Dimensions that decide whether a tank fits
Capacity is rarely the constraint. These are:
- The delivery route. Doorway width, stair diagonal, turning radius in a corridor. Measure the route before the tank arrives.
- Overall height including legs and fittings — and then enough clearance above the fill port to lift a stick out of it.
- Regulated clearances. For propane these are set by water capacity, not by fill level, and they differ between OSHA's Table H-23 and NFPA 58. For oil storage above the SPCC thresholds, secondary containment has to hold the largest single container plus freeboard.
- Floor loading. Contents weight over the tank's own footprint, compared against what the structure is designed for. This is the constraint people most often skip, and the one that is most expensive to discover late.
How the figures on these pages are produced
Dimensions are the standard trade geometry for each class, stated on every page so you can check them against your own tank. Capacities are computed from those dimensions with exact partial-fill formulas — see the methodology page — and they match the corresponding chart pages value for value. Liquid weights use the reference densities tabulated on the methodology page, near 60–70 °F; a 10 °F swing moves a hydrocarbon density by roughly 0.4 %, so treat weights as indicative rather than exact.
Where an individual manufacturer's tank differs from the standard geometry, the manufacturer's data sheet describes your tank and these pages describe the class. Prefer theirs whenever the two disagree and the number matters.
Propane tanks: siting, handling and standards
Siting and clearances
Separation distance is set by water capacity, not by how much propane you keep in the vessel. OSHA's Table H-23 and NFPA 58's Table 6.4.1.1 both work from the container's water capacity in gallons — the number on the nameplate — so a tank kept half empty is sited exactly as a full one.
Distances are measured to the nearest important building or group of buildings and to the property line, and separately between containers. Beyond the headline distance, keep the area within 10 feet clear of weeds and dry grass, keep the relief valve's discharge path away from openings, and give the delivery truck a route that does not require dragging hose past ignition sources.
Underground propane vessels have their own distance rules and their own corrosion protection requirements, and they are not simply the aboveground tank buried. Local amendments are common and frequently stricter than either national document — confirm with the authority having jurisdiction before you pour a pad.
The standards behind propane tanks
Stationary propane containers are pressure vessels built to ASME Boiler and Pressure Vessel Code Section VIII, Division 1. The nameplate stamps the water capacity and design pressure, and on a pressure vessel the nameplate — not a tape measure — is the authoritative capacity. That is why the charts on this site solve the shell length so the computed geometry matches the nameplate rather than the other way round.
Siting is governed by two documents that do not entirely agree. OSHA's 29 CFR § 1910.110, Table H-23 sets minimum distances by water capacity: 10 ft to the nearest important building for containers up to 500 gallons, 25 ft for 501–2,000 gallons (reducible to 10 ft for a single container of 1,200 gallons water capacity or less that is at least 25 ft from any other LP-gas container over 125 gallons), and 50 ft for 2,001–30,000 gallons. Most states adopt NFPA 58 instead or as well, and its Table 6.4.1.1 differs — notably for containers of 125 gallons and under. Confirm which your jurisdiction enforces before siting anything.
Fill limits come from NFPA 58: a container equipped with a fixed maximum liquid level gauge is filled to roughly 80 % of water capacity, leaving vapour space for thermal expansion. Propane's expansion coefficient is about six times water's, which is what that headspace is protecting against.
Common questions
How far does a propane tank have to be from my house?
It depends on water capacity and on which code your jurisdiction enforces. OSHA's Table H-23 requires 10 ft to the nearest important building for containers up to 500 gallons water capacity and 25 ft for 501–2,000 gallons, reducible to 10 ft for a single container of 1,200 gallons or less that sits at least 25 ft from any other LP-gas container over 125 gallons. Most states adopt NFPA 58, whose Table 6.4.1.1 differs for small containers. Confirm locally before siting.
Why can a propane tank only be filled to 80 %?
Because liquid propane expands far more than water for the same temperature rise, and the vapour space above the liquid is what absorbs that expansion. NFPA 58 sets the filling limit, and a container with a fixed maximum liquid level gauge fills to roughly 80 % of its water capacity.
Heating-oil tanks: siting, handling and standards
Siting, fill and service
Three dimensions decide whether a tank fits a real basement, and only one of them is in the capacity: overall height including legs (it has to clear the ceiling and leave room to lift a stick out of the fill port), footprint, and the diagonal it has to travel through the doorway and down the stairs. Measure the route before the tank arrives, not after.
The fill and vent piping matters as much as the tank. Under NFPA 31 the vent must be sized and routed so the tank cannot pressurise during a delivery, and the whistle must be audible at the fill point — a driver who cannot hear the whistle stop is a driver who will overfill. A tank that has been overfilled once has almost certainly had oil in the vent line.
Leave working room at the gauge end. A tank pushed tight into a corner is a tank nobody sticks, and an unstuck tank is where the surprise runs-out come from.
The standards behind heating-oil tanks
An aboveground fuel-oil supply tank of this class is built to UL 80 and installed under NFPA 31, which governs where it may sit, how it is vented and filled, and its clearance to the appliance. The fuel itself is specified by ASTM D396 — that specification's density range is why heating-oil weights are quoted as a band rather than a single figure.
If the tank serves a commercial site rather than a house, 40 CFR § 112 may also apply: the SPCC rule brings in facilities whose aggregate aboveground oil storage capacity exceeds 1,320 US gallons where a discharge could reach navigable waters, and requires secondary containment for the entire capacity of the largest single container plus freeboard for precipitation. Two 275s and a 550 add up to 1,100 gal, under it; a fourth 275 would take that to 1,375 gal, over it.
None of those standards make a gauge chart authoritative. For a measurement that has to survive a dispute, the tank needs a capacity table produced by physical calibration under ISO 7507-1 or the equivalent API chapters.
Underground oil tanks: siting, handling and standards
Siting, backfill and access
Excavation, bedding and backfill matter more than the tank for a buried vessel. The hole has to be big enough for the specified bedding all round, the backfill has to be the material the tank's listing calls for, and the tank has to be held down against flotation — an empty buried tank in a high water table will lift, and a lifted tank breaks its piping.
Plan the gauging access before the tank goes in the ground. You need a riser you can reach with a stick, a known distance from grade to tank bottom, and a fill point a delivery truck can actually reach. Under 40 CFR § 280.43(a) the gauging equipment has to resolve the full tank height to the nearest eighth of an inch, and that is much easier to arrange at installation than to retrofit.
Record the as-built: tank dimensions, orientation, any deliberate slope, the riser height, and the depth to the tank bottom. Every future reconciliation depends on those four numbers, and they are unrecoverable once the hole is closed.
The standards behind underground oil tanks
Buried fuel tanks sit inside a federal regulatory programme, 40 CFR Part 280, and a tank chart is part of how compliance is demonstrated. Under § 280.43(a), inventory control must be capable of detecting a release of 1.0 % of flow-through plus 130 gallons in a month, and the gauging equipment must read the full height of the tank to the nearest one-eighth of an inch. That is the specification your stick and your chart together have to meet.
Manual tank gauging is allowed as the sole release-detection method only for tanks of 550 gallons or less nominal capacity, and for some 551–1,000 gallon tanks that meet the diameter criteria in § 280.43(b). Larger tanks need it in combination with, or replaced by, another method. State programmes approved under 40 CFR Part 281 are often stricter than the federal floor.
Construction is to UL 58 for steel USTs (or UL 1746 for jacketed steel), and installation to NFPA 31 where the tank feeds oil-burning equipment. For a capacity table you can defend, calibrate under ISO 7507 rather than computing from nominal dimensions.
Common questions
What do I need to record when an underground tank is installed?
Tank dimensions, orientation, any deliberate slope, riser height and the depth from grade to tank bottom. Every later inventory reconciliation depends on those numbers and none of them are recoverable once the excavation is backfilled.
IBC totes: siting, handling and standards
Handling, stacking and what the marking tells you
Read the UN marking before you trust the label. It records the design type, the packing group, the rated capacity in litres, the maximum gross mass and the date of manufacture — and for a regulated shipment it also carries a periodic retest date. A cage stencilled '275 gallon' tells you what it was sold as; the marking tells you what it is approved for.
Gross mass is the constraint people hit first. A full 275 gal tote of water is about 1,040 kg before the pallet, which puts it beyond many hand pallet trucks and most mezzanine floors. Check the forklift rating and the floor, not just the doorway.
Stack only to the marked stacking test load, only on level ground, and only with the lower tote full — a part-filled bottle deflects under load and the cage is not the structural element people assume it is.
The standards behind IBC totes
Intermediate bulk containers used for regulated materials are built, marked and periodically retested under 49 CFR Part 178, Subpart N. The UN marking moulded into the bottle and stamped on the cage records the design type (a caged plastic tote is a composite IBC), the packing group it is approved for, the rated capacity in litres, the maximum gross mass, and the date of manufacture. That marking is the authoritative capacity — a '275 gallon' label on the cage is a trade name.
IBCs also carry a retest interval. An out-of-date tote may be perfectly serviceable for water in a yard and unusable for a regulated shipment, and the marking is where you check.
Where totes are stored outdoors at a facility subject to the SPCC rule, 40 CFR § 112.8(c)(11) treats them as portable containers requiring secondary containment sized for the largest single container plus freeboard for precipitation.
Aquariums: rated size, real volume and floor loading
Floor loading: what the comparison means
A filled aquarium is one of the densest point loads people put in a house. The comparison worth doing is against the code design load, not against your intuition.
Each aquarium size page compares its load over its own footprint with the 40 lb/ft² habitable-room figure in IRC Table R301.5. Exceeding that figure is not a prediction of failure. Framing carries a safety factor, the load spreads through the subfloor and the joists, and code live load is a uniform design assumption rather than a collapse threshold. It does mean the question is worth asking properly for anything in this class on a suspended floor — the answers depend on joist size, span, direction and how close the tank sits to a bearing wall. Orient the stand across the joists rather than along a single one, and get a structural opinion before putting a large tank on an upper storey.
From rated size to actual water volume
Work down from the label in three steps and you will land within a few percent of the truth. Start with the geometric figure on the aquarium's size page, which is the brim-full internal volume. Subtract the air gap you actually run — an inch below the trim is typical and is real volume you do not have. Then subtract displacement: substrate counts for roughly 60–70 % of its bulk volume once pore water is accounted for, and rock and hardscape count for essentially all of theirs.
The result matters because almost every aquarium decision is dosed per unit of water: medication, fertiliser, water changes, and stocking guidance. Dosing to the label when the tank is actually running 15 % short is a 15 % overdose — enough to matter for anything with a narrow therapeutic window.
The reliable way to settle it once: fill from empty through a metered hose or in counted buckets and write the number on the back of the stand. Every subsequent dose is then arithmetic rather than estimation.
What governs an aquarium's rated size
Nothing, in the sense that applies to a pressure vessel or a fuel tank. Aquarium 'gallon' ratings are trade nominal figures based on exterior dimensions, brim full. There is no listing standard behind them and no obligation on a manufacturer to hit the number. The only fixed quantity in the whole calculation is the gallon itself — exactly 231 cubic inches, per NIST Handbook 44, Appendix C.
The standard that does bite is structural. IRC Table R301.5 designs residential floors for a 40 lb/ft² live load in habitable rooms other than sleeping rooms, and 30 lb/ft² in sleeping rooms. A filled aquarium concentrates far more than that over its own small footprint — see the floor-loading figure on each aquarium's size page. Whether that matters depends on joist direction, span and where the tank sits relative to a bearing wall, which is a question for someone who can look at the framing.
Common questions
Can my floor take a large aquarium?
Compare the loading figure on the aquarium's size page against the 40 lb/ft² habitable-room design live load in IRC Table R301.5. Exceeding it is not automatically a problem — framing carries a safety factor and the load spreads — but it is the point at which the question deserves a real answer based on joist span, direction and proximity to a bearing wall rather than a rule of thumb.
Tanks sized by capacity
Choosing proportions
Each capacity page lists the pairs of dimensions that hold its volume. Choosing between them is a trade between three things:
- Gauging resolution. A short, fat tank has more gallons per inch, so every reading error costs more. A tall, thin tank resolves finely but is harder to stick and easier to tip.
- Footprint and head height. Doubling the diameter quarters the length needed for the same volume, so small diameter changes move the length a lot. Check the delivery route, not just the final position.
- Structural load. The weight on each capacity page is the contents alone, concentrated over whatever footprint you pick. Halving the footprint doubles the pressure on the slab or the framing underneath it.
For horizontal cylinders there is a fourth: the volume-per-inch curve is steepest at mid-height and shallowest at both ends, so on a horizontal tank a reading error costs the most gallons around half full and the fewest near empty or full.
The standards behind a capacity figure
The gallon itself is exact: 231 cubic inches, by definition in NIST Handbook 44, Appendix C. Everything downstream of that is geometry, and the geometry on each capacity page is exact for the dimensions it states.
What is not exact is any real tank. For a capacity table that will hold up in a dispute or an audit, the tank must be calibrated by physical measurement under ISO 7507-1 (manual strapping) or the equivalent API MPMS chapters, with corrections for plate thickness, shell expansion and tank tilt. Computed geometry is the right tool for design, sizing and sanity-checking a supplier's sheet; it is not a calibration.
Notes that apply to every tank
Common questions
Is the rated capacity the same as the real capacity?
Rarely exactly. The rating is a trade label; the geometric figure on each size page is what its stated dimensions actually hold. Both are useful — just be clear which one you are quoting when the number leaves your desk.
Sources and standards
These are the documents behind the units, the listings and the siting rules referenced across the dimension library. Individual size pages cite the subset that applies to that tank.
- Handbook 44, Appendix C — General Tables of Units of MeasurementNational Institute of Standards and Technology, U.S. Department of Commercehttps://www.nist.gov/document/2026-nist-handbook-44-appendix-cThe legal-metrology reference for U.S. customary units. Fixes the U.S. liquid gallon at exactly 231 cubic inches and tabulates the full liquid-volume chain (minim → fluid dram → fluid ounce → gill → pint → quart → gallon).
- Special Publication 811, Appendix B.8 — Factors for Units Listed AlphabeticallyNational Institute of Standards and Technologyhttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b8NIST's master table of conversions into SI. Factors printed in boldface are exact by definition rather than measured or rounded — which is how you tell a defined unit from an approximated one.
- 29 CFR § 1910.110 — Storage and handling of liquefied petroleum gases (Table H-23, minimum distances)U.S. Occupational Safety and Health Administration, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-H/section-1910.110Federal separation distances for LP-gas containers, by water capacity: under 125 gal — 10 ft above ground; 125–250 gal — 10 ft; 251–500 gal — 10 ft and 3 ft between containers; 501–2,000 gal — 25 ft (reducible to 10 ft for a single container of 1,200 gal water capacity or less, if it is at least 25 ft from any other LP-gas container over 125 gal); 2,001–30,000 gal — 50 ft.
- NFPA 58 — Liquefied Petroleum Gas Code (separation distances, Table 6.4.1.1; filling limits, Ch. 7)National Fire Protection AssociationPaid standard — cited by designation; obtain from the publisher.The model code most US states adopt for propane installations, and the one your local inspector is most likely working from. It is not identical to OSHA's Table H-23 — notably for containers of 125 gal water capacity and under — so confirm which is enforced locally. NFPA publishes free read-only access to its codes at nfpa.org.
- ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 — Rules for Construction of Pressure VesselsAmerican Society of Mechanical EngineersPaid standard — cited by designation; obtain from the publisher.Stationary propane containers are ASME vessels. The nameplate stamps water capacity, design pressure and the manufacturer's data — and the nameplate, not a tape measure, is the authoritative capacity for a pressure vessel.
- UL 80 — Standard for Steel Tanks for Oil-Burner Fuel and Other Combustible Liquids; UL 58 — Steel Underground Tanks for Flammable and Combustible LiquidsUL Standards & EngagementPaid standard — cited by designation; obtain from the publisher.The construction standards behind the familiar 275 and 330 gallon aboveground heating-oil tanks (UL 80) and steel USTs (UL 58). They govern steel gauge, seams, fittings and leak testing — not gauge-chart accuracy, which is why a listed tank still needs its own capacity table for anything measured.
- NFPA 31 — Standard for the Installation of Oil-Burning EquipmentNational Fire Protection AssociationPaid standard — cited by designation; obtain from the publisher.Governs how fuel-oil supply tanks are installed, vented, filled and located, including tank-to-appliance clearances and fill and vent piping. Adopted, often with amendments, by most US states.
- ASTM D396 — Standard Specification for Fuel OilsASTM InternationalPaid standard — cited by designation; obtain from the publisher.Defines the grades of fuel oil, including No. 2 heating oil. It sets the density and viscosity ranges this site uses for weight and thermal-expansion figures — which is why a heating-oil weight is a range rather than a single number.
- 40 CFR Part 280 — Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage TanksU.S. Environmental Protection Agency, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-I/part-280The whole federal UST programme: design and construction standards (§ 280.20), release detection (Subpart D), operator training and closure. State programmes approved under Part 281 may be stricter.
- 49 CFR § 178.504 — Standards for steel drums (and § 178.502, identification codes)U.S. Pipeline and Hazardous Materials Safety Administration, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-49/subtitle-B/chapter-I/subchapter-C/part-178/subpart-L/section-178.504The current federal standard for steel drums. Codes are 1A1 (non-removable head) and 1A2 (removable head); openings over 3 inches make a drum removable-head by definition. The legacy DOT-17E designation was superseded by these UN performance-oriented standards.
- 49 CFR Part 178 — Specifications for Packagings (Subpart N: Intermediate Bulk Containers)U.S. Pipeline and Hazardous Materials Safety Administration, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-49/subtitle-B/chapter-I/subchapter-C/part-178Design, construction, marking and periodic retest requirements for IBCs. The UN marking moulded into a tote's bottle records its design type, packing group, test date and rated capacity — read it before trusting a nominal gallon figure.
- 40 CFR § 112.8(c)(2) — Spill Prevention, Control, and Countermeasure Plan requirements for onshore facilitiesU.S. Environmental Protection Agency, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-D/part-112/subpart-B/section-112.8Requires secondary containment sized for the entire capacity of the largest single container, plus sufficient freeboard to contain precipitation. Note that the rule itself does not state “110 %” — that is a common design convention layered on top of the regulatory floor.
- International Residential Code, Table R301.5 — Minimum uniformly distributed live loadsInternational Code Council (free read-only access at codes.iccsafe.org)https://codes.iccsafe.org/s/IRC2021P2/chapter-3-building-planning/IRC2021P2-Pt03-Ch03-SecR301.5Residential floors are designed to 40 lb/ft² live load in habitable rooms other than sleeping rooms, and 30 lb/ft² in sleeping rooms. A filled aquarium concentrates far more than that over its own footprint, which is why the comparison is worth doing before siting one upstairs.
- Methodology — the partial-fill formulas and liquid densities used on this sitetankvolumecalc.comhttps://tankvolumecalc.com/methodology/Every chart value here comes from a closed-form partial-fill formula, not interpolation: circular segments for cylinders, a piecewise obround model for 275/330 heating-oil tanks, and scaled spherical caps for dished heads. Densities and their bases are tabulated there.
- 40 CFR § 280.43 — Methods of release detection for tanksU.S. Environmental Protection Agency, via the electronic Code of Federal Regulationshttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-I/part-280/subpart-D/section-280.43The federal rule that makes tank charts a compliance instrument rather than a convenience. Inventory control must detect a release of 1.0 % of flow-through plus 130 gallons per month; gauging equipment must read the full tank height to the nearest one-eighth of an inch; manual tank gauging is allowed as the sole release-detection method only for tanks of 550 gallons or less (and some 551–1,000 gallon tanks meeting the diameter criteria).
Every linked source above was retrieved and checked on 2026-09-02. Factors quoted as exact are exact by definition in the cited document, not rounded by us.